Free Field Blueprint — Sodium Hypochlorite
The bleach pump stops feeding, gets replaced, and the problem comes back. This is the 12-page blueprint for why that happens, what to check first, and the two spec decisions that keep the gas out of the pump head.
Sodium hypochlorite decomposes on its own and releases gas. Tacmina publishes the decomposition as 2NaClO to 2NaCl + O2 and describes hypochlorite as a chemical that readily decomposes into a gas. Blue-White describes the same behavior from the pump side, noting that chemicals which offgas can create air pockets that cause vapor locking. A reciprocating metering pump moves a fixed displacement per stroke and depends on an incompressible liquid; when a gas pocket occupies the pump head, the stroke compresses and expands that pocket instead of pushing chemical through the discharge check. Tacmina calls the end state gas lock, where no liquid is discharged at all even with a reciprocating diaphragm.
A published US wastewater plant case reports pumps that worked satisfactorily at higher chemical flow rates but repeatedly vapour locked at lower flows. At a low stroke rate, gas enters the pump head at the rate the chemistry produces it while the pump sweeps the head far less often, so gas production outpaces gas removal. Blue-White describes the same mechanism when it warns that on an oversized or too-slow pump, gas can accumulate in the pump head without being pushed through. This is why installing a larger pump usually makes the problem worse rather than better.
If the pump runs correctly right after you manually bleed it, then gradually loses output, and bleeding the head again produces a slug of gas followed by chemical, suspect gas binding before the diaphragm or the calibration. A failed diaphragm does not restore full output when you bleed it.
Poly Processing names iron, copper, cobalt and nickel as accelerators of hypochlorite degradation, and its own general specification for 9 to 15 percent sodium hypochlorite states that an IMFO outlet is strongly recommended for full drainage of sodium hypochlorite to prevent sediment build up. Poly describes the Integrally Molded Flanged Outlet as a homogenous flange system molded as part of the tank, positioned at the bottom of the sidewall below the tank knuckle radius, which it says gives full tank discharge. A tank that never fully drains keeps a sediment heel where those metals concentrate, and a decomposing heel is a gas source feeding the same suction line.
Blue-White states that peristaltic pumps are very effective when dosing fluids that contain trapped gases because they are not affected by air bubbles, that bubbles simply pass through the pump tube, and that there is no vapor lock and no loss of prime. On the FLEXFLO A3 specifically Blue-White states it cannot vapor lock or lose prime. Both are manufacturer claims with no published test method behind them and should be treated as such. Blue-White does not make a hypochlorite-specific vapor-lock claim on its A3 product pages; the hypochlorite link comes separately from its Flex-A-Prene tube compatibility statement, which describes the tube as chemically resistant to 25 percent sodium hypochlorite.
Free PDF — 12 Pages
Enter your work email and the PDF opens immediately. No cost, and no sales call attached to it.
01 · The failure is a fluid property
What hypochlorite does on its own, and the four things that accelerate it — every one of them a storage or layout decision, not a pump decision.
02 · Why the pump reads gas as dead
Gas lock explained from the displacement side, the two separate paths to it, and the field symptom that separates it from a failed diaphragm.
03 · The five-step check, in order
Flooded suction, line length and size, high points, liquid end selection, and where the purged gas actually goes.
04 · Storage: Poly Processing Vertical IMFO
The outlet position, the sediment argument in Poly's own spec language, the SG rating, vent sizing, gaskets, and why the schedule clock starts at drawing approval.
05 · Feed: Blue-White FLEXFLO A3
Published flow, turndown, pressure, temperature and tube-compound data — and where the 2,500:1 turndown does real work against the low-flow failure mode.
06 · What these sources do not say
Nine places where a claim is commonly made and the manufacturer source does not support it. Read this before quoting anything.
James Riggins
LibertyCES — Liberty Chemical Equipment & Supply
30+ years in industrial chemical systems, reviewing real process conditions before a part number ever gets recommended. Send the tank location, purchased concentration, dose range, and the suction run as it is actually piped — that's enough to tell whether you have a suction-path problem or a selection problem. No charge to look at a spec before the PO goes out.
(559) 395-5500 ·[email protected] ·[email protected] ·libertyces.com