Chemical compatibility is documented for Food/Beverage/Biological Process Fluids. Documented models include GF Signet 2819 Sanitary, GF Signet 2820 Sanitary and GF Signet 2821 Sanitary. Send James the fluid, concentration, temperature and flow for a free spec review.

30+ years spec experience. Send James the process data and get a real answer — not a catalog page.

Request a Spec Review →
0 sector applications

Where LibertyCES specs Sanitary Conductivity / Resistivity Electrode

No documented sector-specific application yet for this category — treat as a spec-review item until real field data exists.

1 chemical compatibility record

Chemical compatibility

Food/Beverage/Biological Process Fluids

Multi-source documented
USP/WFI purified waterboiler condensateCIP solution strength verificationbeverage-grade process water
Materials: 316SS or Titanium, >RA25 surface finish (sanitary variants) · EPDM O-rings · 1-1.5in or 2in Tri-Clamp process connection · 130°C @ 5.2 bar (sanitary rating) · PEEK insulator (2823) · Hastelloy-C, Monel and Titanium available on special order for the 2818-2823 family
GF Signet 2819 Sanitary (0.01 cell constant) · GF Signet 2820 Sanitary (0.1) · GF Signet 2821 Sanitary (1.0) · GF Signet 2823 (20.0 cell, 200-400,000 µS — the only cell constant in the family explicitly rated for acids/bases, cleaners and other concentrated chemicals) · GF Signet 2850 universal sensor electronics (EasyCal automatic test-solution recognition, extends sensor-to-instrument distance to 120m/400ft)

Models

Sanitary Conductivity / Resistivity Electrode: models in the LibertyCES catalog

5 models across 1 product line from 1 manufacturer.

Manufacturer-stated values from the documents cited in the last column. A blank cell means the document doesn’t state it. Confirm exact options with a spec review.
Model / lineManufacturerTypeSize / capacity / flowPressureTemperatureWetted materialSource
Conductivity/Resistivity Electrodes
2818-2821 Standard Conductivity Electrodes
Georg Fischer (GF Signet)Instrumentation0.055uS-10000uS (0.01-1.0 cell)100–200 psi (6.9–13.8 bar)212–248 °F (100–120 °C)316SS or Titanium body, PTFE insulator, EPDM O-ringsGF Signet — Instrumentation Product Range Brochure
Conductivity/Resistivity Electrodes
2822-2823 High Conductivity Electrodes
Georg Fischer (GF Signet)Instrumentation100uS-400000uS (10.0-20.0 cell)100 psi (6.9 bar)203–302 °F (95–150 °C)CPVC or 316SS body, PEEK insulator, EPDM O-ringsGF Signet — Instrumentation Product Range Brochure
Conductivity/Resistivity Electrodes
2819-2823 Sanitary Conductivity Electrodes
Georg Fischer (GF Signet)Instrumentation0.055uS-400000uS75 psi (5.2 bar)to 266 °F (to 130 °C)316SS or Titanium, EPDM O-rings, Tri-ClampGF Signet — Instrumentation Product Range Brochure
Conductivity/Resistivity Electrodes
2839-2842 PVDF Dual-Threaded Conductivity Electrodes
Georg Fischer (GF Signet)Instrumentation0.055uS-200000uS (0.01-10.0 cell)40 psi (2.8 bar)to 268 °F (to 131 °C)316SS electrodes, PVDF insulator/connection, FKM O-ringGF Signet — Instrumentation Product Range Brochure
Conductivity/Resistivity Electrodes
2850 Conductivity/Resistivity Sensor Electronics
Georg Fischer (GF Signet)Instrumentationn/auniversal, all Signet conductivity electrodesPBT, CPVCGF Signet — Instrumentation Product Range Brochure

This table is part of the equipment catalog dataset (CSV and JSON).

FAQ

Frequently Asked Questions

Can Sanitary Conductivity / Resistivity Electrode handle Food/Beverage/Biological Process Fluids?

Sanitary Conductivity / Resistivity Electrode has documented compatibility with Food/Beverage/Biological Process Fluids Materials to confirm: 316SS or Titanium, >RA25 surface finish (sanitary variants), EPDM O-rings, 1-1.5in or 2in Tri-Clamp process connection, 130°C @ 5.2 bar (sanitary rating), PEEK insulator (2823), Hastelloy-C, Monel and Titanium available on special order for the 2818-2823 family. Specific chemicals include USP/WFI purified water, boiler condensate, CIP solution strength verification, beverage-grade process water.

How do I specify Sanitary Conductivity / Resistivity Electrode for my application?

Send LibertyCES your fluid, chemistry, concentration, temperature, flow, pressure, and suction conditions for a free spec review of Sanitary Conductivity / Resistivity Electrode against your actual process data — not a generic catalog match.

Spec Review

Send LibertyCES the process data, not a part number

Fluid, chemistry, concentration, temperature, flow, pressure, line size, and current equipment — that's what a real spec review needs to start.

Ready to buy or need a fast answer? Call, text, or email James directly — (559) 395-5500 · [email protected].

Sensing & Control

Other sensing & control categories

Chlorine / Chlorine Dioxide Analyzer PanelChrome Reduction / Cyanide Destruction Control SystemClamp-On Ultrasonic Flow MeterConductivity / Resistivity ElectrodeControllerController / Process AnalyzerFlow MeterHydrostatic Level SensorLevel InstrumentMagmeter / Paddlewheel / Turbine Flow MeterOptical Dissolved Oxygen SensorPool / Aquatic Facility ControllerPressure / Leak Monitoring RTUPressure InstrumentRadar / Ultrasonic / Hydrostatic Level TransmitterRadar Level TransmitterSCADA / Remote Monitoring IntegrationSight GlassTemperature SensorToxic / Combustible Gas DetectorWater MeterpH / ORP ElectrodepH/ORP Instrument
Free spec review

Send James your spec

Fluid, concentration, temperature, flow or volume, and where it goes. James replies with a real answer, not a catalog page.

Reviewed by James Riggins, 30+ years specifying water and chemical process equipment · Updated