Case Study / Industrial Wastewater pH Control

Cleaning Up: Automated Wastewater pH Treatment System

Transforming non-compliant discharge at 3.3 pH into city-approved effluent in the 5.5–6.5 pH compliant range — fully automated, zero operator guesswork.

3.3 → 5.5–6.5
pH, Non-Compliant to Approved
20K–40K
GPD Treated
Up to $25K/day
Civil Penalty Exposure Avoided
Direct answer

A small manufacturing plant discharged 20,000 to 40,000 gallons a day of wastewater at pH 3.3, below the 5.0 federal floor. The solution was a fully automated two-stage system: a 4,500-gallon Snyder holding tank in double containment, ProMinent radar and pH sensing, and PLC-controlled dosing. Effluent now lands in the compliant 5.5–6.5 pH range.

Key facts

At a glance

Facts as stated on this page. Nothing here is added to the write-up below.
Process / fluidAcidic wastewater inflow at 3.3 pH
ConcentrationAcidic discharge at 3.3 pH treated to a municipal-compliant 5.5–6.5 pH range
ApplicationFully automated two-stage industrial wastewater pH neutralization
EquipmentProMinent metering pumps, radar level sensors, pH sensors and Dialog X PLC controller
MaterialsPolyethylene chemical storage tanks with double-wall secondary containment
Operating conditionsDaily volume of 20,000–40,000 GPD
ProblemWastewater at pH 3.3, below the 5.0 federal floor
Solution4,500-gallon Snyder holding tank in double containment, ProMinent radar and pH sensing, PLC-controlled dosing
OutcomeEffluent now lands in the compliant 5.5–6.5 pH range
Project Snapshot
Client Type
Small Manufacturing Plant
Inflow pH
3.3 pH (Acidic)
Target Discharge
5.5–6.5 pH (Compliant Range)
Daily Volume
20,000–40,000 GPD
System Type
Fully Automated 2-Stage System
Summary — For Engineers & Facility Managers

This system is a fully automated two-stage industrial wastewater pH neutralization solution designed to treat 20,000–40,000 gallons per day of acidic discharge (3.3 pH) and deliver consistent municipal-compliant effluent within the 5.5–6.5 pH range using closed-loop chemical dosing, continuous mechanical mixing, and PLC-controlled conditional discharge authorization.

pH Scale — System Reference Points
3.3 pH
Inflow
5.0 pH
Federal Floor
5.5 pH
Muni Min.
5.5–6.5 pH
Target Out
7.0 pH
Neutral

Under federal pretreatment rules, discharging wastewater below a pH of 5.0 into a public sewer is prohibited unless the system is specifically designed to handle it.

Financial exposure: $1,000–$5,000+/day in municipal administrative penalties, up to $25,000/day in civil penalties

Stage 1 — Primary Containment

Inflow & Holding — The FOG Tank

The wastewater is initially diverted into a 4,500-gallon Snyder holding tank, designated as the FOG tank — Stage 1, the intake and buffer point for all corrosive inflow before any active treatment occurs. To mitigate the risk of vessel failure, the holding tank is placed within a double containment setup, ensuring that even in the event of a tank rupture or seal failure, no acidic material escapes to the environment or drainage system.

A ProMinent radar unit is installed on the tank to provide continuous, non-contact level monitoring — tracking the liquid level in real time and triggering the transfer pump automatically at a preset level of approximately 115 inches.

Stage 1 — FOG TankTechnical Reference
Vessel4,500-Gallon Snyder Holding Tank
ContainmentDouble-Wall Secondary Containment
Level SensorProMinent Radar Unit (AP05) — Non-Contact
Transfer Trigger~115 inches → auto-activates transfer pump
pH MonitoringProMinent pH Sensor (AP00) — Inflow Measurement
Field Photos
Dual 4,500-gallon Snyder tanks inside double containment area for wastewater pH treatment
ProMinent radar level sensor mounted on Snyder tank for continuous wastewater level monitoring
Elevated view of Snyder wastewater tanks with orange ProMinent radar level sensor mounted on top
ProMinent pH system control panel with Dialog X PLC controller, field installation
Equipment Used

Key System Components

ProMinent radar level sensor mounted on Snyder tank, official field photo
ProMinent Fluid Controls

Metering pumps, radar level sensors, pH sensors, and the Dialog X PLC controller driving the automated 2-stage dosing sequence.

View manufacturer →
Grovhac industrial mixer, official product photo
Grovhac

Industrial mixers providing chemical dispersion within the treatment vessels.

View manufacturer →
Georg Fischer / GF Signet flow sensor panel, official product photo
Georg Fischer

Electromagnetic flow meters providing real-time flow measurement for dosing control.

View manufacturer →
Dual Snyder 4,500-gallon wastewater pH treatment tanks inside double containment area
Snyder Industries

Dual 4,500-gallon polyethylene chemical storage tanks with double-wall secondary containment.

View manufacturer →
FAQ

Wastewater pH Treatment FAQ

What pH range is required for municipal wastewater discharge?

Under federal pretreatment rules, discharging wastewater below a pH of 5.0 into a public sewer is prohibited unless the system is specifically designed to handle it. This system targets a 5.5–6.5 pH compliant range.

What happens if a facility discharges out-of-range wastewater?

Financial exposure ranges from $1,000–$5,000+ per day in municipal administrative penalties and up to $25,000/day in civil penalties.

What is the FOG tank in this system?

The FOG tank is a 4,500-gallon Snyder holding tank that serves as Stage 1 — the intake and buffer point for all corrosive inflow before any active treatment occurs, placed inside double-wall secondary containment.

How does the system know when to start treatment?

A ProMinent radar unit provides continuous, non-contact level monitoring on the holding tank, automatically triggering the transfer pump at a preset level of approximately 115 inches.

Spec Review

Don't leave your compliance to guesswork.

James Riggins — zero spec failures across 30+ years, 100+ projects

See exactly how automated pH neutralization protects your operations from crippling fines.

Free spec review

Send James your spec

Fluid, concentration, temperature, flow or volume, and where it goes. James replies with a real answer, not a catalog page.

Reviewed by James Riggins, 30+ years specifying water and chemical process equipment · Updated